摘要

Measurements of infiltration through different size entrances of a cold store at two different cold store temperatures were taken and compared against established analytical models and computational fluid dynamics (CFD) models. The analytical and CFD models generally tended to over predict the infiltration. The analytical model developed by Gosney et al. [Proc. Inst. Refrig. 72 (1975) 31] provided the closest comparison with the various experiments. The CFD models were more accurate than the fundamental analytical models but less accurate than those based on a semi-empirical approach. For the experimental configurations examined, CFD offered no real advantage over these empirical analytical models. If the conditions were such that the infiltration rate changed with time or if door protection devices (e.g. air curtains) were used, CFD would become much more advantageous in predicting infiltration.
机译:进行了在两个不同的冷库温度下通过冷库的不同尺寸入口的渗透测量,并将其与已建立的分析模型和计算流体力学(CFD)模型进行了比较。分析模型和CFD模型通常倾向于过度预测渗透率。 Gosney等人开发的分析模型。 [过程研究所Refrig。 72(1975)31]提供了与各种实验的最接近的比较。 CFD模型比基本分析模型更准确,但不如基于半经验方法的模型准确。对于所检查的实验配置,CFD并没有提供超过这些经验分析模型的真正优势。如果条件使得渗透率随时间变化或使用门保护装置(例如气帘),则CFD在预测渗透率方面将变得更加有利。