首页> 外文期刊>International Journal of Refrigeration >Effect of twisted tape insert on heat transfer and pressure drop in horizontal evaporators for the flow of R-134a
【24h】

Effect of twisted tape insert on heat transfer and pressure drop in horizontal evaporators for the flow of R-134a

机译:扭曲的胶带插入物对水平蒸发器中R-134a流动的传热和压降的影响

获取原文
获取原文并翻译 | 示例
           

摘要

An experimental study has been carried out on the heat transfer enhancement and pressure drop characteristics in presence of twisted tape inserts, during flow boiling of R-134a, inside a horizontal evaporator. The test-evaporator was an electrically heated 1260 mm long copper tube with 7.5 mm inside diameter. The experiments were performed for plain flow and four tubes with twisted tapes of 6, 9, 12 and 15 twist ratios and four refrigerant mass velocities of 54, 85, 114 and 136 kg/s m{sup}2 for each tape. It has been found that the twisted tape inserts enhance the heat transfer coefficient on relatively higher pressure drop penalty, in comparison to that for the plain flow.
机译:在水平蒸发器内,在R-134a的流动沸腾过程中,在存在扭曲的带状插入物的情况下,已经进行了关于传热增强和压降特性的实验研究。测试蒸发器是电加热的1260毫米长的铜管,内径为7.5毫米。对于平流和四个具有扭曲比为6、9、12和15的扭曲带的管以及每个带的四个制冷剂质量速度分别为54、85、114和136 kg / s m {sup} 2的实验进行了实验。已经发现,与普通流动相比,扭曲的带状插入物以相对较高的压降损失来提高传热系数。