This paper presents the combined void fraction models on the basis of flow pattern to choose suitable models for calculating the two-phase refrigerant mass of R410A air conditioners, and the model is validated experimentally. The existing single void fraction models are also evaluated experimentally. The Taitel-Dukler flow pattern map is recommended to use in the combined void fraction models. The results presented herein show that the calculated refrigerant mass using the combined void fraction models agrees relatively better with the measured refrigerant mass than that of the single void fraction models. T-B model (for intermittent flow) and Premoli model (for annular flow) are recommended for calculating the two-phase refrigerant mass in evaporator, and T-B model (for intermittent flow) and Harms model (for annular flow) are also indicated for calculating the two-phase refrigerant mass in condenser.
机译:本文提出了基于流型的组合空隙率模型,选择合适的模型来计算R410A空调的两相制冷剂质量,并对该模型进行了实验验证。现有的单一空隙率分数模型也通过实验进行评估。建议将Taitel-Dukler流型图用于组合的空隙率模型。本文给出的结果表明,使用组合的空隙率模型计算出的制冷剂质量与测得的制冷剂质量相比要好于单个空隙率模型。建议使用TB模型(用于间歇流动)和Premoli模型(用于环形流动)来计算蒸发器中的两相制冷剂质量,还建议使用TB模型(用于间歇流动)和Harms模型(用于环形流动)来计算蒸发量。冷凝器中的两相制冷剂质量。